Home / Products / Modular Air-Source Gas Engine Heat Pump (GHP)
Commercial Series (70 kW – 210 kW)

Modular Air-Source Gas Engine Heat Pump (GHP)

A robust, outdoor packaged heat pump unit powered by an industrial natural gas engine. Delivers simultaneous or switchable hydronic cooling, space heating down to -25°C (-13°F), and up to 85°C (185°F) domestic hot water using 100% engine thermal recovery.

Heating Rating: 71 kW to 210 kW (240k – 716k BTU/h)
Cooling Rating: 62 kW to 185 kW (17.6 – 52.6 Tons)
Aux. Electric Power: 3.2 kW – 5.5 kW (3-Phase)
GasXys GHP Series Outdoor Skid Acoustic Insulated Galvanized Enclosure (68 dB(A))
BACnet / Modbus RTU Dual-Fuel Capable

Technical Specifications

Multi-Capacity Engineering Schedule

Dual-unit reporting: SI Metric and US Imperial units.

Model Parameter GX-GHP-70 GX-GHP-105 GX-GHP-140 GX-GHP-210
Rated Heating Capacity (@ 7°C / 45°C DB) 71.0 kW (242 MBH) 105.0 kW (358 MBH) 142.0 kW (484 MBH) 210.0 kW (716 MBH)
Low-Ambient Heating (@ -15°C / 5°F) 62.5 kW (213 MBH) 92.0 kW (314 MBH) 125.0 kW (426 MBH) 186.0 kW (634 MBH)
Rated Cooling Capacity (@ 35°C / 7°C DB) 62.0 kW (17.6 RT) 93.0 kW (26.4 RT) 124.0 kW (35.2 RT) 185.0 kW (52.6 RT)
Primary Energy Ratio (PER - Heating) 1.48 1.50 1.52 1.55 (Up to 1.75 w/ DHW)
Natural Gas Consumption (Nm³/h @ Full Load) 4.9 Nm³/h (185 SCFH) 7.2 Nm³/h (272 SCFH) 9.6 Nm³/h (363 SCFH) 14.2 Nm³/h (537 SCFH)
Auxiliary Power Supply (Voltage / Phase) 208-230V / 460V, 3-Phase, 60Hz (North America) OR 400V, 3-Phase, 50Hz (Europe)
Connected Electrical Load 2.8 kW 3.8 kW 4.6 kW 5.5 kW only
Domestic Hot Water Max Leaving Temp Up to 85°C (185°F) via Plate Heat Exchanger using Engine Jacket Water
Sound Pressure Level (A-Weighted @ 1m) 65 dB(A) 66 dB(A) 68 dB(A) 69 dB(A)
Water Piping Connection (Hydronic Inlet/Outlet) DN50 (2" ANSI Flange) DN65 (2.5" ANSI) DN80 (3" ANSI) DN100 (4" ANSI Flange)

Extreme Cold Climate Engineering

Why GHP Outperforms Electric Heat Pumps Below Freezing

Electric heat pumps suffer up to a 50% capacity loss at -15°C and must reverse their cycle to defrost the outdoor coil, draining heat from the building water loop.

GasXys GHP utilizes Engine Coolant Waste Heat to heat the outdoor coil from behind. Defrost occurs continuously without reversing refrigeration valves and without electric backup heaters.

Continuous Hydronic Output:
Supply water temperature remains steady at 50°C~60°C even during severe sub-zero blizzards.
CAPACITY RETENTION vs AMBIENT TEMPERATURE GHP vs Standard EHP
+7°C (45°F) Design Baseline 100% Output
-7°C (19°F) Winter Condition GHP: 96% | Electric HP: 72%
-15°C (5°F) Severe Cold GHP: 89% | Electric HP: 54%
-25°C (-13°F) Extreme Arctic Vortex GHP: 80% | Electric HP: Offline / Electric Aux

Architectural & MEP Assets

Engineered for Rapid Drawing Inclusion

Download parametric Revit families, 2D/3D CAD outlines, and BMS communication maps.

Autodesk Revit (.RFA)

Parametric 3D BIM models with hydronic & gas connection ports pre-defined.

Request BIM File

AutoCAD 2D/3D (.DWG)

Pad dimensions, lifting lug locations, and service clearance envelopes.

Download DWG Pack

BMS Register Map

Complete BACnet IP / MS-TP and Modbus RTU address lists for building automation.

Download Protocol Map

IOM Manual (PDF)

Comprehensive Installation, Operation & Preventative Maintenance Manual.

Download Manual